Review Date Reviewer's Name Type of Review Description Status Comments
10/24/2014 RONALD BROWN ADA REVIEW Reqs Change For the New Covered Parking Area:
Provide 1 van accessible parking space and accessible route connection to the terminal accessible route. Show all accessible parking requirements as per the 2010 ADASAD including dimensions, markings, sizes, signage, access to the accessible route, grade slopes, accessible parking aisle and any ramps as required.
11/04/2014 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
11/07/2014 ROBERT SHERRY WATER REVIEW Completed
11/07/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide the roof drainage areas that were used to determine the size of the rain water leaders being modified. Reference: Sections 1101, 1106 and 1108, IPC 2012.
2. Verify that the roof drain leaders being modified are not used for collecting rain water from both primary roof drains and secondary roof drains. Reference: 1108.2, IPC 2012.
11/10/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Demonstrate energy code compliance for the alterations to the building envelope (e.g. new fenestration) based on the current code. Reference: Sections C101.4.3, C101.5, C103.2, International Energy Conservation Code 2012.
2. Provide NFRC fenestration product ratings for the U-factor and the SHGC values on COMcheck or use the appropriate default U-factor and SHGC values from Tables C303.1.3 (1) and C303.1.3.(2), IECC 2012. Reference: Section C303.1.3, IEC 2012.
3. A note for AHU-WM refers to sheet M200 for chilled water piping; has the chilled water piping been placed on sheet M301 instead?
4. The condensate from AHU-WM is shown terminating over a roof drain. Verify that the roof drain is not actually an overflow roof drain. Condensate drains may not terminate over a roof drain unless the roof drain terminates at or below grade in an area capable of absorbing the condensate flow without surface drainage. Reference: Section 307.2.1, IMC 2012, as amended by the City of Tucson.
5. The City of Tucson has not adopted ASHRAE Standard 62-1 as an approved method for calculating ventilation requirements. Provide calculations to show that the ventilation system is sized in accordance with Section 403.3, IMC 2012.
11/13/2014 MARTIN BROWN FIRE REVIEW Approved
11/19/2014 KEN VAN KARSEN ELECTRICAL-COMMERCIAL REVIEW Reqs Change T14CM07159

1. Single line diagram of service:
a. Clarify wire size feeding panel MPEA (one line diagram/panel schedule).
b. Clarify main breaker size panel C (one line diagram/panel schedule).
c. Provide wire and conduit sizes feeding the new panels on sheet E914.
2. 2012 IECC (interior) lighting calculation: provide ComCheck report, or Table C405.5.2(1) building area or (2) space-by-space for budget determination.

Ken Van Karsen
Elect Plan Review
PDSD, City of Tucson
520-837-4906
Kenneth.VanKarsen@tucsonaz.gov