Permit Number: T14CM07086
Parcel: 133231460

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM07086
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/22/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET A0: REVISE THE SUMMARY OF GOVERNING REGULATIONS TO THE CURRENT EDITIONS OF THE CODES ENFORCED BY THE CITY OF TUCSON.
10/22/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change The mechanical revisions shown on the floorplan are incomplete; show how the return air is to be handled. Reference: Section 601.2, IMC 2012.
10/22/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Reqs Change 1> REFERENCE THE 2011 NEC AS THE ADOPTED CODE ON PAGE A0

2> INCOMPLETE PLANS: HOW ARE YOU SWITCHING LIGHT IN OFFICE? HOW DOES THIS CONFORM TO 2012 IECC REQUIREMENTS CONCERNING OCCUPANCY SENSORS?
10/22/2014 ROBERT SHERRY WATER REVIEW Completed
10/22/2014 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
10/22/2014 RSHERRY1 WWM REVIEW Passed No wastewater plumbing.
10/22/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
10/29/2014 AROMERO4 ENGINEERING REVIEW Needs Review
10/29/2014 AROMERO4 ZONING REVIEW Needs Review
10/29/2014 AROMERO4 FIRE REVIEW Needs Review