Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T14CM07086
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/22/2014 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET A0: REVISE THE SUMMARY OF GOVERNING REGULATIONS TO THE CURRENT EDITIONS OF THE CODES ENFORCED BY THE CITY OF TUCSON. |
| 10/22/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | The mechanical revisions shown on the floorplan are incomplete; show how the return air is to be handled. Reference: Section 601.2, IMC 2012. |
| 10/22/2014 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | 1> REFERENCE THE 2011 NEC AS THE ADOPTED CODE ON PAGE A0 2> INCOMPLETE PLANS: HOW ARE YOU SWITCHING LIGHT IN OFFICE? HOW DOES THIS CONFORM TO 2012 IECC REQUIREMENTS CONCERNING OCCUPANCY SENSORS? |
| 10/22/2014 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 10/22/2014 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 10/22/2014 | RSHERRY1 | WWM | REVIEW | Passed | No wastewater plumbing. |
| 10/22/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 10/29/2014 | AROMERO4 | ENGINEERING | REVIEW | Needs Review | |
| 10/29/2014 | AROMERO4 | ZONING | REVIEW | Needs Review | |
| 10/29/2014 | AROMERO4 | FIRE | REVIEW | Needs Review |