Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T14CM07066
Parcel: 12801005H

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM07066
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/04/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
11/05/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
11/05/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Completed
11/05/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change The automatic start capability is not the same as having scheduled start times. Section C403.2.4.3.3, IECC 2012 requires the controls to "...be capable of automatically adjusting the daily start time of the HVAC system in order to bring each space to the desired occupied temperature immmediately prior to scheduled occupancy." [Initial comment: Verify that the HVAC unit controls have been provided with an automatic start capability. Reference: Section C403.2.4.3.3, IECC 2012.]
11/13/2014 AROMERO4 WWM REVIEW Completed