Permit Number: T14CM07050
Parcel: 14102013D

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T14CM07050
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/27/2014 RONALD BROWN BUILDING-COMMERCIAL REVIEW Reqs Change Reference Activity Number T14CM07048 for comments
10/30/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Completed
10/31/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide structural calculations for the mounting shelf for the water heater to show that the water heater will be safely supported from the building structure. Reference: Section 301.2, IPC 2012.
2. The rim elevation of the next upstream sanitary manhole (2908.97') is less than 12" below the first floor elevation (2909.00'). Provide a backwater valve per Section 715.1, IPC 2012, as amended by the City of Tucson.
10/31/2014 MARTIN BROWN FIRE REVIEW Approved
10/31/2014 ROBERT SHERRY WATER REVIEW Completed
10/31/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide NFRC fenestration product ratings for the insulated metal swinging doors for the U-factor on COMcheck or use the appropriate default U-factor values from Table C303.1.3.(2), IECC 2012. Reference: Section C303.1.3, IEC 2012.
2. Revise the energy code analysis for the building envelope, coordinating the roof insulation used in the analysis with those shown on the drawing (e.g. no R-values for cavity insulation and no continuous insulation layers were shown on the building sections or details). Reference: Section C303.1, IECC 2012, as amended by the City of Tucson.
3. Clarify the specified EER for heat pump HP2-1 with regard to the Mechanical Compliance Certificate. The unit is scheduled to have a minimum EER of 12.0 but Table C406.2(2), IECC 2012 calls for either a SEER of 12.0 or an EER of 12.4.
4. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012.
11/03/2014 MICHAEL ST. PAUL ZONING REVIEW Reqs Change Approval of DP14-0177 required.
11/03/2014 ELIZABETH LEIBOLD ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
11/18/2014 AROMERO4 OUT TO CUSTOMER Completed