Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - NEW
Permit Number - T14CM07049
Review Name: COMMERCIAL - NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/27/2014 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Reqs Change | Reference Activity Number T14CM07048 for comments |
| 10/29/2014 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Completed | |
| 10/31/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. The rim elevation of the next upstream sanitary manhole (2908.97') is less than 12" below the first floor elevation (2909.50') of rooms 400, 401, 402, and 403. Provide a backwater valve per Section 715.1, IPC 2012, as amended by the City of Tucson. Floors discharging from above that reference point shall not discharge through the backwater valve. 2. Clarify why hot water is not being supplied to the classroom sinks (P-5A). Reference: Section 607.1, IPC 2012. |
| 10/31/2014 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 10/31/2014 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 10/31/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Revise the energy code analysis for the building envelope, coordinating the roof insulation used in the analysis with those shown on the drawing (e.g. no R-values for cavity insulation or continuous insulation layers were shown on the building sections or details). Reference: Section C303.1, IECC 2012, as amended by the City of Tucson. 2. Clarify the specified EER for heat pumps HP 4-1 through HP 4-4with regard to the Mechanical Compliance Certificate. The unit is scheduled to have a minimum EER of 12.1 but Table C406.2(2), IECC 2012 calls for either a SEER of 12.0 or an EER of 12.4. 3. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012. |
| 11/03/2014 | MICHAEL ST. PAUL | ZONING | REVIEW | Reqs Change | Approval of DP14-0177 required. |
| 11/03/2014 | ELIZABETH LEIBOLD | ENGINEERING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/18/2014 | AROMERO4 | OUT TO CUSTOMER | Completed |