Review Details: REVISION - - 2ND
Permit Number - T14CM07048
Review Name: REVISION - - 2ND
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/01/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | . |
| 04/01/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 04/05/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. The specified backflow prevention device, Watts model 007, is not listed for ASSE 1022 as required for coffee machines or non-carbonated beverage dispensers. Clarify what the second Watts 007 backflow preventer shown in the isometric 3/3p2.1 is supplying (i.e. is it also serving coffee machine?). Reference: Section 608.16.10, IPC 2012. 2. Verify that the relief port for the ASSE 1022 backflow preventers are directed to either an approved indirect waste receptor or to the outside, where water leakage will not cause damage. Reference: Section 608.14, IPC 2012. 3. If the ice maker, K105, does not have a listed, integral backflow preventer or an integral air gap conforming to Section 608.13.1, IPC 2012 specify the type of backflow prevention device that is to be provided for the water connection. Reference: Sections 608.1 and 608.3, IPC 2012. |
| 04/15/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved |