Permit Number: T14CM07048
Parcel: 14102013D

Review Status: Completed

Review Details: REVISION - - 2ND

Permit Number - T14CM07048
Review Name: REVISION - - 2ND
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/01/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed .
04/01/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
04/05/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. The specified backflow prevention device, Watts model 007, is not listed for ASSE 1022 as required for coffee machines or non-carbonated beverage dispensers. Clarify what the second Watts 007 backflow preventer shown in the isometric 3/3p2.1 is supplying (i.e. is it also serving coffee machine?). Reference: Section 608.16.10, IPC 2012.
2. Verify that the relief port for the ASSE 1022 backflow preventers are directed to either an approved indirect waste receptor or to the outside, where water leakage will not cause damage. Reference: Section 608.14, IPC 2012.
3. If the ice maker, K105, does not have a listed, integral backflow preventer or an integral air gap conforming to Section 608.13.1, IPC 2012 specify the type of backflow prevention device that is to be provided for the water connection. Reference: Sections 608.1 and 608.3, IPC 2012.
04/15/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved