Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T14CM07040
Parcel: 124120690

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM07040
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/29/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
10/29/2014 ROBERT SHERRY WATER REVIEW Completed
10/29/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed