Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T14CM07018
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/18/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 09/21/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Modify the new notes on sheet A-3 to indicate that the specified maximum U-factors and SHGC values must be determined using NFRC 100 (for the U-values) and NFRC 200 (for the SHGC values). [Initial comment: Provide NFRC fenestration product ratings for the U-factor and the SHGC values on COMcheck or use the appropriate default U-factor and SHGC values from Tables C303.1.3 (1) and C303.1.3.(2), IECC 2012. Reference: Section C303.1.3, IECC 2012.] |
| 09/21/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed |