Permit Number: T14CM07018
Parcel: 13803031T

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T14CM07018
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/18/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
09/21/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Modify the new notes on sheet A-3 to indicate that the specified maximum U-factors and SHGC values must be determined using NFRC 100 (for the U-values) and NFRC 200 (for the SHGC values). [Initial comment: Provide NFRC fenestration product ratings for the U-factor and the SHGC values on COMcheck or use the appropriate default U-factor and SHGC values from Tables C303.1.3 (1) and C303.1.3.(2), IECC 2012. Reference: Section C303.1.3, IECC 2012.]
09/21/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed