Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T14CM07013
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/21/2014 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 10/29/2014 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Reqs Change | GENERAL 1. Several sheets have lettering below that of the City of Tucson's standard of 3/32" minimum, actual size, both upper and lower case. Please revise all architectural, structural, mechanical, plumbing and electrical non-compliant sheets and resubmit. SHEET A601 AND A312 2. Note "C": Where partitions are indicated to terminate 4" above suspended ceilings, these are to be braced to the structure above to meet the code requirements of a 5 psi horizontal load as per Section 1607.14 or provide a letter from the structural engineer calculating analysis of the partitions horizontal load without bracing. 3. Show on the floor plan where details 16/A312 and 17/A312 are being used. SHEET SB1 4. Show the accessible seating as required by the 2012 IBC, Section 1108.2. END OF REVIEW |
| 11/05/2014 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 11/05/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide a direct connection to the building drainage system for all plumbing fixtures except as allowed by Chapter 8, IPC 2012. Reference: Section 301.3, IPC 2012. 2. Verify that separate indirect waste pipes for each compartment of the 3-compartment sink are being provided to protect against cross-contamination or fouling. Reference: Sections 801.2 and 802.1.8, IPC 2012. 3. The mechanical specifications on PM20 show both an "interior" and"exterior" hydromechanical grease interceptor but the specifications are incomplete and the proposed location of the grease interceptor is not shown on the drawings. Clarify how the public sewer is to be protected from harmful discharges. (Note: the under floor plumbing plan, 3/P311, calls out a 4" grease waste line in room 113 which then transforms into a sanitary waste line.) Reference: Section 1003.1, IPC 2012. 4. Verify the temperature of the water discharged from the dishwasher; the maximum discharge temperature shall not exceed 140 degrees Fahrenheit unless approved cooling methods are to be employed prior to introducing the waste flow into the waste piping. Reference: Section 701.7, IPC 2012 5. A dishwasher may not discharge through a hydromechanical grease interceptor but it is required to discharge through a gravity grease interceptor. Reference: Section 1003.3, IPC 2012, as amended by the City of Tucson. |
| 11/05/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide calculations demonstrating adequate ventilation using the current code. Reference: Section 403.2, IMC 2012. 2. Provide general room exhaust for any cooking appliance that does not require the installation of a Type II hood. The minimum exhaust rate shall be 0.70 CFM per square foot, using a minimum area of 100 square feet for each individual appliance. Reference: Section 507.2.2, IMC 2012. |
| 11/14/2014 | KEN VAN KARSEN | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | T14CM07013 1. One line diagram information: notate the AIC rating of existing service equipment for verifying appropriate rating of panel LP-10C. 2. Show the total proposed lighting power as less than the removed lighting power for determining power budget compliance, 2012 IECC: C101.4.3 exception 7, or show a calculation for Table C405.5.2(1) building area or (2) space-by-space budget compliance. Ken Van Karsen Elect Plan Review PDSD, City of Tucson 520-837-4912 Kenneth.VanKarsen@tucsonaz.gov |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/24/2014 | SHANAE POWELL | OUT TO CUSTOMER | Completed |
| 11/24/2014 | CPIERCE1 | REJECT SHELF | Completed |