Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T14CM07003
Parcel: 12709011M

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM07003
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/17/2014 MICHAEL ST. PAUL ZONING REVIEW Approved
10/17/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
10/17/2014 KEN VAN KARSEN ELECTRICAL-COMMERCIAL REVIEW Completed
10/17/2014 ROBERT SHERRY WATER REVIEW Completed
10/17/2014 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
10/17/2014 RSHERRY1 WWM REVIEW Passed No wastewater plumbing.
10/17/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
10/17/2014 JASON GREEN ENGINEERING REVIEW Approved
10/17/2014 MARTIN BROWN FIRE REVIEW Approved
10/17/2014 RONALD BROWN COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed