Permit Number: T14CM06975
Parcel: 14118620A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM06975
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/16/2014 DAVID RIVERA ZONING REVIEW Approved
10/16/2014 LOREN MAKUS ENGINEERING REVIEW Approved
10/16/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET A-1; FLOOR PLAN KEYNOTES: NOTES 5 AND 7 WERE NOT LOCATED ON THE PLAN. VERIFY.
2. SHEET A-1; WALL LEGEND: WALL W3 INDICATES TO PROVIDE 6" STUDS AT A SIMILAR CONDITION. WHERE IS THIS SIMILAR CONDITION?
3. SHEET A-2; REFLECTED CEILING PLAN KEYNOTES: NOTES 4 AND 5 WERE NOT LOCATED ON THE PLAN. VERIFY.
4. SHEET A-1; WALL LEGEND: WALL W3 INDICATES WALL BRACING AT 48" O.C. PROVIDE A DETAIL ON THE DRAWING INDICATING THE BRACING SIZE AND CONNECTION TO THE TOP OF THE PARTITION AND TO THE STRUCTURE ABOVE.
5. SHEET A-2; DETAIL 3: THIS DEMISING WALL MUST MEET THE REQUIREMENTS OF A FIRE PARTITION PER THE IBC SECTION 708. REVISE THE DETAIL.
6. SHEET A-2; TOILET PLAN: THE PLAN INDICATES NOTE 12 (GRAB BAR) IN THE VICINITY OF THE LAVATORY. REVISE.
7. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
10/16/2014 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
10/17/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
10/17/2014 KEN VAN KARSEN ELECTRICAL-COMMERCIAL REVIEW Completed
10/17/2014 ROBERT SHERRY WATER REVIEW Completed
10/17/2014 MARTIN BROWN FIRE REVIEW Approved
10/17/2014 SPOWELL1 WWM REVIEW Needs Review
10/17/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide a design for the gas service to the rooftop units.