Permit Number: T14CM06938
Parcel: 134010490

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T14CM06938
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/05/2014 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Reqs Change PLAN REVIEW COMMENTS
Date: 11-06-14
Activity: T14CM06938
Address: 474 S Harrison Rd
Applicant: James Yurek

This letter reflects comments to be addressed. The purpose of this review is to verify compliance to the 2012 International Residential Code with local amendments. In order to facilitate a shorter back check time, we request that you please provide two complete sets of revised plans and calculations, along with a written response to each of the noted items indicating action taken. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:
1. The City of Tucson has adopted the 2012 International family of codes. Correct references to the 2006 IRC on sheet G-100.

FLOOR PLAN:
2. Doors between a garage and a residence shall be self-closing minimum 20-minute fire-rated, R302.5.1.

SECTIONS - DETAILS:
3. Indicate impermeable insulation applied tight to the roof sheathing to a value specified in Table R806.5.

MECHANICAL PLAN:
4. Provide Manual J/S/D calculations for the forced air unit in accordance with M1401.3, M1601.1.

ELECTRICAL PLAN:
5. Specify GFCI protection for receptacle at garage ceiling, E3902.
6. Indicate the location of the carbon monoxide detector, R315.

INTERNATIONAL ENERGY CONSERVATION CODE:
7. Specify high-efficacy lamps for at least 75% of all lighting fixtures, N1104.1.
8. Show hot water pipe with minimum R-3 insulation, N1103.4.2.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Clayton.Trevillyan@tucsonaz.gov
Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
11/07/2014 AROMERO4 OUT TO CUSTOMER Completed