Permit Number: T14CM06919
Parcel: 10608002C

Address:
841 W PRINCE RD

Review Status: Active

Review Details: COMMERCIAL - TI

Permit Number - T14CM06919
Review Name: COMMERCIAL - TI
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
10/15/2014 DAVID RIVERA ZONING REVIEW Approved
10/15/2014 LOREN MAKUS ENGINEERING REVIEW Approved
12/12/2014 KEN VAN KARSEN ELECTRICAL-COMMERCIAL REVIEW Completed
12/12/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide cooling and heating load calculations for the replacement heat pumps.
2. Provide the mechanical compliance certificate for the replacement heat pumps.
12/12/2014 RONALD BROWN BUILDING-COMMERCIAL REVIEW Reqs Change Provide conmplete architectural construction documents as per the 2012 IBC and 2009 ICC A117.1 and as listed below but not limited to:
1. Provide large scale toilet plans and elevations showing all accessible requirements.
2. Provide door and window schedules
3. Detail room divider partition details
4. Provide wall sections
5. Provide interior elevations of all casework
6. Show elevation and section of reception counter
7. Where are water dispensers
8. Where is mop sink
9. Where is water heater
10. Provide complete code analysis
11. Define all existing and new elements
12. Show existing entrance as shown and approved on site plan
13. Provide building sections.
END OF REVIEW
12/12/2014 ROBERT SHERRY WATER REVIEW Reqs Change Verify that no size change is needed for the water meter.
12/12/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Show how the new water heater is to be supprted and how maintenance access is to be provided.
12/12/2014 RSHERRY1 WWM REVIEW Needs Review
12/12/2014 MARTIN BROWN FIRE REVIEW Approved
12/12/2014 RONALD BROWN COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed