Review Status: Active
Review Details: COMMERCIAL - TI
Permit Number - T14CM06919
Review Name: COMMERCIAL - TI
Review Status: Active
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/15/2014 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 10/15/2014 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 12/12/2014 | KEN VAN KARSEN | ELECTRICAL-COMMERCIAL | REVIEW | Completed | |
| 12/12/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide cooling and heating load calculations for the replacement heat pumps. 2. Provide the mechanical compliance certificate for the replacement heat pumps. |
| 12/12/2014 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Reqs Change | Provide conmplete architectural construction documents as per the 2012 IBC and 2009 ICC A117.1 and as listed below but not limited to: 1. Provide large scale toilet plans and elevations showing all accessible requirements. 2. Provide door and window schedules 3. Detail room divider partition details 4. Provide wall sections 5. Provide interior elevations of all casework 6. Show elevation and section of reception counter 7. Where are water dispensers 8. Where is mop sink 9. Where is water heater 10. Provide complete code analysis 11. Define all existing and new elements 12. Show existing entrance as shown and approved on site plan 13. Provide building sections. END OF REVIEW |
| 12/12/2014 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Verify that no size change is needed for the water meter. |
| 12/12/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Show how the new water heater is to be supprted and how maintenance access is to be provided. |
| 12/12/2014 | RSHERRY1 | WWM | REVIEW | Needs Review | |
| 12/12/2014 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 12/12/2014 | RONALD BROWN | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |