Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T14CM06562
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/03/2014 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 10/03/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 10/03/2014 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Completed | |
| 10/03/2014 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 10/03/2014 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Completed | |
| 10/03/2014 | LHANLY1 | WWM | REVIEW | Passed | |
| 10/03/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 10/03/2014 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 10/03/2014 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 10/03/2014 | LHANLY1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Completed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/06/2014 | CPIERCE1 | APPROVAL SHELF | Completed |
| 10/06/2014 | AROMERO4 | OUT TO CUSTOMER | Completed |