Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T14CM06525
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/21/2014 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 10/21/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 10/24/2014 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved |