Permit Number: T14CM06525
Parcel: 129042620

Address:
2020 E 13TH ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM06525
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/17/2014 KEN VAN KARSEN ELECTRICAL-COMMERCIAL REVIEW Completed
10/17/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
10/17/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Revise the size of the water distribution piping to limit the water velocity to less than 8 FPS. Use the water fixture units from Table E103.3(2), 2012 IPC. If PEX is to be used, show the sizes that will be required for PEX also.
2. Provide a cleanout at the juinction of the building drain and the building sewer
10/21/2014 AROMERO4 ZONING REVIEW Needs Review
10/21/2014 AROMERO4 BUILDING-COMMERCIAL REVIEW Needs Review