Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T14CM06525
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/17/2014 | KEN VAN KARSEN | ELECTRICAL-COMMERCIAL | REVIEW | Completed | |
10/17/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
10/17/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Revise the size of the water distribution piping to limit the water velocity to less than 8 FPS. Use the water fixture units from Table E103.3(2), 2012 IPC. If PEX is to be used, show the sizes that will be required for PEX also. 2. Provide a cleanout at the juinction of the building drain and the building sewer |
10/21/2014 | AROMERO4 | ZONING | REVIEW | Needs Review | |
10/21/2014 | AROMERO4 | BUILDING-COMMERCIAL | REVIEW | Needs Review |