Permit Number: T14CM06525
Parcel: 129042620

Address:
2020 E 13TH ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM06525
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/02/2014 AROMERO4 WWM REVIEW Completed
10/03/2014 MARTIN BROWN FIRE REVIEW Approved
10/03/2014 ROBERT SHERRY WATER REVIEW Completed
10/03/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Reqs Change Plan review has been completed and the following corrections are required. Please provide a written response to comments with plan re-submittal.

1) Provide lumen calculations for all exterior luminaires on the site (lumens / acre) in accordance with the City of Tucson Outdoor Lighting Code.
2) Exterior luminaires are limited to 3500K color temperature. Plans indicate 4000K fixtures.
3) EF1 in restroom may be switched with a programmable timer or interconnected with the AC.


If there are questions regarding this review contact:

LeeRay
520-837-4906
LeeRay.Hanly@tucsonaz.gov
10/03/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide heating and cooling load calculations that justify the capacity of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012.
2. Revise the sequence of operation for the restroom exhaust fan so that all of the air supplied to the restrooms will be exhausted. Reference: Section 403.2.1 (4), IMC 2012.
3. Revise the mechanical design as required to avoid using the corridor as a return air duct. Reference: Section 601.2, IMC 2012.
10/03/2014 RONALD BROWN BUILDING-COMMERCIAL REVIEW Reqs Change
10/03/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Revise the size of the water distribution piping to limit the water velocity to less than 8 FPS. Use the water fixture units from Table E103.3(2), 2012 IPC. If PEX is to be used, show the sizes that will be required for PEX also.
2. Provide a cleanout at the juinction of the building drain and the building sewer.
10/03/2014 RONALD BROWN COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
10/17/2014 JASON GREEN ENGINEERING REVIEW Approved
10/17/2014 SPOWELL1 ZONING REVIEW Needs Review