Permit Number: T14CM06498
Parcel: 10511061R

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T14CM06498
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/31/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Completed
11/03/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. PREVIOUS COMMENT 5; SHEET A0.01; CODE ANALYSIS CHAPTER 10 (COMMON PATH OF EGRESS TRAVEL): THE DRAWINGS INDICATE THE LONGEST COMMON PATH OF TRAVEL IN THE BUILDING IS 100'-0", WHILE THE IBC TABLE 1014.3 INDICATES 75' IS THE MAXIMUM ALLOWED ("ALL OTHERS" OCCUPANCY). ADDRESS THIS ISSUE.
2. PREVIOUS NOTE 13; SHEET A1.40: KEYED NOTE 22 REFERENCES A SIGN AT THE ELECTRICAL ROOM. THAT ROOM (AND NOTE 22) ARE NOT SHOWN ON THIS SHEET. CLARIFY.
3. PREVIOUS NOTE 14; SHEETS A1.42 AND A1.43: BOTH SHEETS CONTAIN VERBIAGE AND NUMBERS THAT STILL DO NOT MEET THE CITY OF TUCSON REQUIREMENTS OF A MINIMUM OF 3/32" IN HEIGHT (UPPER AND LOWER CASE). REVISE.
4. PREVIOUS NOTE 15; SHEET A1.46: THIS SHEET CONTAINS VERBIAGE AND NUMBERS THAT STILL DO NOT MEET THE CITY OF TUCSON REQUIREMENTS OF A MINIMUM OF 3/32" IN HEIGHT (UPPER AND LOWER CASE). REVISE.
5. SHEET A3.10; DETAIL 07: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE VERBIAGE.
6. PREVIOUS COMMENT 16; SHEET A4.01 (DETAILS 08 AND 09): AT THE METAL STUD BRACES, THE SIZE AND QUANTITY OF CONNECTORS AT THE VERTICAL STUDS WERE NOT PROVIDED. IN ADDITION, A DETAIL OF THE BRACE CONNECTION TO THE EXISTING STRUCTURE ABOVE WAS NOT INCLUDED.
7. PREVIOUS COMMENT 18; SHEET A4.11 (DETAILS 04, 05, 09, AND 11): AT THE METAL STUD BRACES, THE SIZE AND QUANTITY OF CONNECTORS AT THE VERTICAL STUDS WERE NOT PROVIDED. IN ADDITION, A DETAIL OF THE BRACE CONNECTION TO THE EXISTING STRUCTURE ABOVE WAS NOT INCLUDED.
8. SHEET S-101; ELEVATION 4: A BOXED NOTE INDICATES TO REFERENCE THE ARCHITECT FOR GATE DETAILS. THOSE DETAILS WERE NOT LOCATED. COORDINATE WITH THE ARCHITECT.
9. SHEET S-101 (SECTION 2); STRUCTURAL CALCULATIONS (CMU6): THE WALL FOOTING IN THE CALCULATIONS INDICATES A 16" THICKNESS, WHILE THE SECTION INDICATES A 1'-3" FOOTING THICKNESS. CLARIFY.
10. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
11/06/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
11/06/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Comment not resolved; the minimum font height is 3/32" for all of the characters, even the lower case characters. See M-2 and M-4. [Initial comment: Revise the font size used on the drawings to a minimum height of 3/32-inch (i.e. both upper and lower case fonts must be at least 3/32" high). Reference: Section 107.2.1, IBC 2012.]

Final Status

Task End Date Reviewer's Name Type of Review Description
11/14/2014 SHANAE POWELL OUT TO CUSTOMER Completed
11/14/2014 FERNE RODRIGUEZ REJECT SHELF Completed