Permit Number: T14CM06494
Parcel: 110101540

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T14CM06494
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/28/2014 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Reqs Change PLAN REVIEW COMMENTS
Date: 10-31-14
Activity: T14CM06494
Address: 4950 E. Pie Allan Ct.
Applicant: John Riggs

This letter reflects comments to be addressed. The purpose of this review is to verify compliance to the 2012 International Residential Code with local amendments. In order to facilitate a shorter back check time, we request that you please provide two complete sets of revised plans and calculations, along with a written response to each of the noted items indicating action taken. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

PLUMBING PLAN:
1. Provide the maximum developed length of the gas supply system measured from the meter to the furthest appliance served, G2413.1, Table G2413.4 (1).
2. Specify the total demand of the gas supply system by indicating all gas-fired appliances served by the gas meter.
3. Specify the size of the water meter, the maximum developed length of water line from the meter the furthest appliance served and the lowest available working pressure, P2903.7.
4. Provide a water fixture unit schedule for the entire property (including existing) to determine the total demand on the water supply system, P2903.6. Note: The Tucson Water policy adopted 7/13/12 limits the maximum demand for a 5/8" water meter to 15 GPM; confirm with Tucson Water that the existing meter will be able to meet the proposed water demand. Reference Tables P2903.6 and P2903.6 (1), IRC 2012.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Clayton.Trevillyan@tucsonaz.gov
Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
12/17/2014 CPIERCE1 REJECT SHELF Completed