Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T14CM06483
Parcel: 138192370

Address:
368 W ELVIRA RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T14CM06483
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/16/2014 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Reqs Change PLAN REVIEW COMMENTS
Date: 12-16-14
Activity: T14CM06483 2nd review
Address: 368 W. Elvira Rd
Applicant: Nogales Builders LLC

This letter reflects comments to be addressed. The purpose of this review is to verify compliance to the 2012 International Residential Code with local amendments. In order to facilitate a shorter back check time, we request that you please provide two complete sets of revised plans and calculations, along with a written response to each of the noted items indicating action taken. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

INCLUSIVE HOME DESIGN:
1. Provide a complete set of notes on the plan to meet the Inclusive Home Design Ordinance 10463.
2. Provide an accessible route from the public way extending throughout the entire first floor (except for exempt areas as defined in section 1003.3), 1003.2. Vertical changes in floor elevation may not exceed ¼ inch (½ inch when beveled), 1003.4.
3. All pass-through door openings on the accessible route shall have a net width of not less than 30 inches (2'8" door) 1003.5.2.1.

STRUCTURAL / FRAMING PLAN:
4. Provide either a portal frame design for the front of the garage wall or alternate braced wall panels with foundation hold-downs at both ends of each panel, Table R602.10.6.1.

PLUMBING PLAN:
5. All construction drawings submitted after March 1, 2009 for one- or two-family dwellings require a solar water heating system, or future installation preparation with one of the following provisions: control and ¾"water piping; 3" metallic sleeve; or an accessible attic over the water heater, Ordinance 10549.

MECHANICAL PLAN:
6. Provide Manual S/D calculations for the forced air unit in accordance with M1401.3, M1601.1.

ELECTRICAL PLAN:
7. Heating and cooling loads must be calculated at 100% on the electrical load calculation for determining the service panel size, E3602.2.

OUTDOOR LIGHTING CODE
8. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 3.1.2. Include all exterior fixtures on the property in the calculations. Model plans should specify a minimum lot size for the proposed exterior lighting.
9. Provide cut sheets for all FCO fixtures showing the angle of cutoff, light emissions and fixture wattage. All other fixtures are assumed to be unshielded (non-FCO style) 104.2.
10. Exterior lighting within 25 feet of adjacent residential property lines must be fully shielded, 401.3.3.

INTERNATIONAL ENERGY CONSERVATION CODE:
11. Specify high-efficacy lamps for at least 75% of all lighting fixtures, N1104.1.
12. Correct the value specified for the S.H.G.C. of the windows. The value must be expressed as a maximum instead of a minimum, N1102.1.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Clayton.Trevillyan@tucsonaz.gov
Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
12/18/2014 SHANAE POWELL OUT TO CUSTOMER Completed
12/18/2014 CPIERCE1 REJECT SHELF Completed