Review Date Reviewer's Name Type of Review Description Status Comments
10/13/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
10/13/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
10/13/2014 KEN VAN KARSEN ELECTRICAL-COMMERCIAL REVIEW Completed
10/13/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide justification for not including an economizer for the specified heat pumps (if humidity control is required, provide the humidity specifications and show how it will be controlled). The minimum SEER for heat pumps with cooling capacities of less than 65,000 BTUH is 13.0, as shown on the COMcheck Mechanical Compliance certificate on sheet M4.