Permit Number: T14CM06407
Parcel: 10309018A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM06407
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/08/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. STRUCTURAL CALCULATIONS: SHEET 2 INDICATES THE LATERAL RESISTANCE FOR THIS STRUCTURE IS BY THE WALL PANELS. PROVIDE AN ANALYSIS FOR THE WALL PANEL INDICATING IT CAN TRANSFER APPLIED LATERAL LOADS. GENERAL NOTE 5 INDICATES A MANUFACTURER DESIGN FOR 5 PSF. VERIFY NEW LATERAL LOADS ARE LESS THAN 5 PSF, AND SHOW THE MANUFACTURER CALCULATION.
2. STRUCTURAL CALCULATIONS; SHEET 2: THE SOIL IS LISTED AS 2000 PSF BEARING CAPACITY. THE IBC ALLOWS 1000 PSF FOR FOUNDATIONS 12" DEEP, OR 1500 PSF FOR FOUNDATIONS 18" DEEP. REVISE.
3. GENERAL: ALL LETTERING (UPPER AND LOWER CASE) SHALL BE A MINIMUM OF 3/32" IN HEIGHT. VERIFY ALL LETTERING MEETS THAT CRITERIA.
4. SHEET A1.2; KITCHEN ELEVATION: REVISE THE FLOOR TO COUNTER TOP DIMENSION TO 2'-10".
5. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
10/08/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change The specified water heater is a storage-type water heater. Revise the detail of the water heater installation, to include the excess pressure relief, expansion tank, safety pan, and valves. Reference: Sections 503, 504, 606.1, and 607.3, IPC 2012.
10/08/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Reqs Change Provide occupancy sensors and dimming controls per IECC section 405
10/08/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide outside air from outside of the building. reference: Section 202 (Outside air), IMC 2012.
2. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012.
3. Show the size, routing, and termination point for the new condensate drains from the roftop units. Reference: Section 307.2.1, IMC 2012, as amended by the City of Tucson.
10/13/2014 GERRY KOZIOL WWM REVIEW Passed