| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/08/2014 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. STRUCTURAL CALCULATIONS: SHEET 2 INDICATES THE LATERAL RESISTANCE FOR THIS STRUCTURE IS BY THE WALL PANELS. PROVIDE AN ANALYSIS FOR THE WALL PANEL INDICATING IT CAN TRANSFER APPLIED LATERAL LOADS. GENERAL NOTE 5 INDICATES A MANUFACTURER DESIGN FOR 5 PSF. VERIFY NEW LATERAL LOADS ARE LESS THAN 5 PSF, AND SHOW THE MANUFACTURER CALCULATION. 2. STRUCTURAL CALCULATIONS; SHEET 2: THE SOIL IS LISTED AS 2000 PSF BEARING CAPACITY. THE IBC ALLOWS 1000 PSF FOR FOUNDATIONS 12" DEEP, OR 1500 PSF FOR FOUNDATIONS 18" DEEP. REVISE. 3. GENERAL: ALL LETTERING (UPPER AND LOWER CASE) SHALL BE A MINIMUM OF 3/32" IN HEIGHT. VERIFY ALL LETTERING MEETS THAT CRITERIA. 4. SHEET A1.2; KITCHEN ELEVATION: REVISE THE FLOOR TO COUNTER TOP DIMENSION TO 2'-10". 5. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 10/08/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | The specified water heater is a storage-type water heater. Revise the detail of the water heater installation, to include the excess pressure relief, expansion tank, safety pan, and valves. Reference: Sections 503, 504, 606.1, and 607.3, IPC 2012. |
| 10/08/2014 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Provide occupancy sensors and dimming controls per IECC section 405 |
| 10/08/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide outside air from outside of the building. reference: Section 202 (Outside air), IMC 2012. 2. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012. 3. Show the size, routing, and termination point for the new condensate drains from the roftop units. Reference: Section 307.2.1, IMC 2012, as amended by the City of Tucson. |
| 10/13/2014 | GERRY KOZIOL | WWM | REVIEW | Passed |