Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T14CM06407
Parcel: 10309018A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM06407
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/29/2014 KEN BROUILLETTE FIRE REVIEW Approved
09/29/2014 JASON GREEN ENGINEERING REVIEW Approved September 29, 2014
FLOODPLAIN USE PERMIT NO.: T14OT01237
ADDRESS: 3781 N Highway Dr Tucson, Arizona 85705
PROPERTY OWNER: Daveck Properties LLC
PO Box 603 Tempe, Arizona 85280

The applicant is authorized to use a portion of the FEMA Special Flood Hazard Area Zone AO1 floodplain per the Flood Insurance Rate Maps 04019C1669L, specifically described as:

A portion of Parcel 103-09-018A

For the purpose of installing a modular building with the foot print of an existing conforming structure.

The applicant agrees to comply with City of Tucson Floodplain and Erosion Hazard, and Watercourse Amenities, Safety and Habitat regulations, and is particularly bound by the conditions stated below. Violation of any of the conditions stated or referred to below, as determined by the City Engineer, shall be grounds for revocation of this permit. Responsibility for renewal of this permit, if necessary, is with the applicant. Issuance of this permit does not constitute a waiver of other requirements contained in the Tucson City Code, Unified Development Code, or any other Federal, State, County, or local regulation. No use other than as permitted herein is allowed. Additional uses allowed under City of Tucson Floodplain and Erosion Hazard Regulations and Watercourse Amenities, Safety, and Habitat regulations require the issuance of an additional Floodplain Use Permit.

Per the approved grading plan, FFE Elevation and Drainage Report prepared by Entranco Engineers the existing building is in conformance with the NFIP and has a set Finish Floor Elevation. The building finals and the approved Elevation Certificate (T02OT01784) prepared by Edgar Reynolds and Associates dated 21NOV03 confirms that the building was constructed per the site plan making it a conforming structure.

All proposed work is to be on the existing foot print of the existing building and no work shall be completed outside of the building without submitting new plans and permits to verify conformance with Chapter 26 of the Tucson Code.

Renewal of this permit will require a new application, review and approval of that application by the City of Tucson, Planning & Development Services Department, Engineering Division. This permit may be renewed for up to one year at the sole discretion of the City Engineer or designated representatives.

This Floodplain Use Permit will be automatically revoked and becomes invalid if conditions are not complied with, as set forth in this permit.


APPLICANT NAME: Dave Wilmore
ADDRESS: 3 South 59th Ave Phoenix, Arizona 85043
PHONE: 602-269-1188
CONTRACTOR: Storage Equipment Systems
ADDRESS: 3 South 59th Ave Phoenix, Arizona 85043
PHONE: 602-269-1188

(EXPIRATION DATE) Month: 09 Day: 29 Year: 2015

SIGNATURE OF APPLICANT DATE
The applicant is authorized by the City Engineer to receive a floodplain use permit subject to the above referenced conditions and restrictions.
09/29/2014 RONALD BROWN BUILDING-COMMERCIAL REVIEW Reqs Change 1. Need to submit site plan
2. Provide total building plan
3. Submit total A,S,M,P,E construction documents for a single permit issuance.
4. Apply for an Approval for Review permit.
09/29/2014 RONALD BROWN COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
10/08/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide outside air from outside of the building. reference: Section 202 (Outside air), IMC 2012.
2. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012.
3. Show the size, routing, and termination point for the new condensate drains from the roftop units. Reference: Section 307.2.1, IMC 2012, as amended by the City of Tucson.
10/08/2014 SPOWELL1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
10/08/2014 ROBERT SHERRY WATER REVIEW Completed
10/08/2014 MICHAEL ST. PAUL ZONING REVIEW Approved
10/08/2014 SPOWELL1 WWM REVIEW Needs Review
10/08/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change The specified water heater is a storage-type water heater. Revise the detail of the water heater installation, to include the excess pressure relief, expansion tank, safety pan, and valves. Reference: Sections 503, 504, 606.1, and 607.3, IPC 2012.