Review Details: WALK THRU - COMM

Permit Number - T14CM06195
Review Name: WALK THRU - COMM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/30/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET P2.01; DETAIL 1: A NOTE ON THIS DETAIL INDICATES TO ANCHOR THE WATER HEATER FRAME TO THE WALL. PROVIDE THAT DETAIL ON THE ARCHITECTURAL SHEET, INCLUDING CONNECTOR SIZE AND NUMBER.
2. SHEET P2.01; DETAIL 1: STRUCTURAL CALCULATIONS MUST BE ADDED TO VERIFY THAT THE CAPACITY OF THE EXISTING ROOF MEMBERS ARE ADEQUATE TO SUPPORT THE NEW LOAD. PROVIDE A DETAIL INDICATING HOW THE SUPPORT RODS ARE CONNECTED TO THE EXISTING STRUCTURE.
10/01/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
10/01/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed