Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T14CM06195
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/18/2014 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 09/18/2014 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 09/19/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Clarify the source of drinking water. The plumbing plans show a wall box for a point of use water dispenser but the architectural floor plan calls out a "freestanding bottled water cooler" instead. 2. Provide water hammer arrestors for the installation of the clothes washer. 3. Provide cleanouts sized per the size of the pipes they serve (e.g. for the 3" pipe). 4. The fixture drain serving an automatic clothes washer shall connect to a fixture branch that is at least 3 inches in diameter. Reference: Section 406.2, IPC 2012. 5. Provide the fixture descriptions that were not supplied by the architect. |
| 09/19/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Revise the ventilation calculations to include the occupant density and the exhaust airflow rate specified in Table 403.3, IMC 2012 for a beauty salon. 2. Clarify how the source capture exhaust system will be arranged to serve the two nail stations. 3. The area exhaust required for a beauty salon shall operate continuously during the op[erating hours of the salon. |
| 09/19/2014 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET A0.00; CODE ANALYSIS DATA: THE OCCUPANT LOAD IS REFERENCED TO THE IBC SECTION 1004.1.1. REVISE THAT REFERENCE. 2. SHEET A0.0; CODE ANALYSIS DATA: THE EXIT WIDTH IS REFERENCED TO THE IBC TABLE 1005.1. REVISE THAT REFERENCE. 3. SHEET A0.00; CODE ANALYSIS DATA: THE DISTANCE TO THE EXIT IS REFERENCED TO THE IBC TABLE 1019.2. REVISE THAT REFERENCE. 4. SHEET A0.00; CODE ANALYSIS DATA: THE AISLE WIDTH IS REFERENCED TO THE IBC SECTION 1014.4.1. REVISE THAT REFERENCE. 5. GENERAL: PROVIDE A DETAIL ON THE DRAWINGS THAT PROVIDES FOR THE LATERAL BRACING TO RESIST THE REQUIRED 5 PSF LATERAL LOAD. 6. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 09/19/2014 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 09/19/2014 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 09/19/2014 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 09/22/2014 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Completed | |
| 09/30/2014 | CPIERCE1 | WWM | REVIEW | Completed |