Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/24/2014 | MARTIN BROWN | FIRE | REVIEW | Denied | Unable to determine which racks are 96" tall and which are 196" tall. (details sheets 2 & 3). Please clarify. Be advised that any storage above 12' AFF is classified as high piled storage under the International Fire Code. Please review chapter 32 of the 2012 IFC for requirements. Will need to provide an analysis of commodities stored. |
10/07/2014 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
11/05/2014 | AROMERO4 | OUT TO CUSTOMER | Completed |
11/05/2014 | CPIERCE1 | REJECT SHELF | Completed |