Permit Number: T14CM06169
Parcel: 110113620

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM06169
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/18/2014 STEVE SHIELDS ZONING REVIEW Approved
09/18/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Revise the ventilation calculations using more appropriate categories (e.g. dance floor, not retail).
09/18/2014 KEN VAN KARSEN ELECTRICAL-COMMERCIAL REVIEW Completed
09/18/2014 ROBERT SHERRY WATER REVIEW Completed
09/18/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
09/18/2014 ELEIBOL1 ENGINEERING REVIEW Approved TI - with door removal and minor exterior work.
09/18/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Show how the water heater platform is connectred to the building structure.
2. Detail 3/P2.1 shows a recirculation system for the hot water. If so, show the recirulation piping on the plans.
09/18/2014 MARTIN BROWN FIRE REVIEW Approved
09/18/2014 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/24/2014 FRODRIG2 WWM REVIEW Passed