Permit Number: T14CM06078
Parcel: 11706067A

Address:
220 N 4TH AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T14CM06078
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/22/2014 MARTIN BROWN FIRE REVIEW Approved
10/22/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
10/23/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Comment not resolved. The hanging weight of the hood is 419 pounds without the weight of personnel working in or on the hood but the calculations are based on a total weight of 400 pounds. Detail 6/S1.1 does not appear to support the hood as recommended by the manufacturer. [Initial comment: Provide structural calculations to show that the Type I hood is supported from the building structure in accordance with Section 507.6, IMC 2012 (the hood hanging weight plus the weight of personnel working in or on the hood). Clarify how detail 6/S1.1 complies with the support method recommended by the hood manufacturer. Reference: Section 302.1, IMC 2012.]
10/23/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed