Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/22/2014 | MARTIN BROWN | FIRE | REVIEW | Approved | |
10/22/2014 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
10/23/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Comment not resolved. The hanging weight of the hood is 419 pounds without the weight of personnel working in or on the hood but the calculations are based on a total weight of 400 pounds. Detail 6/S1.1 does not appear to support the hood as recommended by the manufacturer. [Initial comment: Provide structural calculations to show that the Type I hood is supported from the building structure in accordance with Section 507.6, IMC 2012 (the hood hanging weight plus the weight of personnel working in or on the hood). Clarify how detail 6/S1.1 complies with the support method recommended by the hood manufacturer. Reference: Section 302.1, IMC 2012.] |
10/23/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed |