Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T14CM06016
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/31/2014 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 10/31/2014 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Completed | |
| 11/03/2014 | STEVE SHIELDS | ZONING | REVIEW | Denied | PDSD TRANSMITTAL FROM: Steve Shields Lead Planner PROJECT: Chapman Honda T14CM06016 Building Plan (2nd Review) TRANSMITTAL DATE: November 3, 2014 1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 2. Zoning has reviewed the building plans but cannot approve until a development package has been approved. 3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved development package. Additional comments may be forthcoming. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 |
| 11/04/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Revise detail 13/P5.0 to show the gas shutoff valve located immediately upstream of the sediment trap. Reference: Section 408.4, IFGC 2012. [Initial comment: Revise detail 13/P5.0 to show that it refers to water heaters WH-2 and WH-3 instead of electric water heater WH-1.] 2. Including the effect of the adjacent vertical wall and the two parapet walls, the effective roof area appears to be greater than 2,000 square feet and at a slope of 1/16" per foot, an 8" semi-circular gutter is required. Reference: Table 1106.6, IPC 2012. [Initial comment: The architectural roof plan shows a 5" gutter with a single downspout of unknown size serving the Detail Bay (161). Provide the size of the downspout and the slope of the gutter. Reference: Section 1106.6, IPC 2012.] |
| 11/05/2014 | ELEIBOL1 | ENGINEERING | REVIEW | Approved | See grading permit for conditions. Engineering will stamp plans after all other reviewers are approved. |
| 11/05/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 11/06/2014 | KEN BROUILLETTE | FIRE | REVIEW | Denied | Unable to locate Hazardous Material Inventory Statement referenced in response letter. |