Permit Number: T14CM05975
Parcel: 136406740

Address:
9610 E 22ND ST

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T14CM05975
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/23/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
09/23/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Comment not addressed. Revise the sequence of operation for the restroom exhaust fan so that all of the air supplied to the restrooms will be exhausted (i.e. the fan shall be running during all periods of occupancy, even if the lights are off). Reference: Section 403.2.1 (4), IMC 2012.
2. Replot M300 - it is gibberish.
09/23/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Completed
09/23/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide the listing information for the specified temperature mixing valve - it is not available on the internet. [Initial comment: Provide tempered water for the lavatories and public hand-washing sinks in restrooms using approved devices conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2012.]

Final Status

Task End Date Reviewer's Name Type of Review Description
09/26/2014 FERNE RODRIGUEZ OUT TO CUSTOMER Completed