Permit Number: T14CM05975
Parcel: 136406740

Address:
9610 E 22ND ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM05975
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/11/2014 STEVE SHIELDS ZONING REVIEW Approved
09/11/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Revise the sequence of operation for the restroom exhaust fan so that all of the air supplied to the restrooms will be exhausted (i.e. the fan shall be running during all periods of occupancy, even if the lights are off). Reference: Section 403.2.1 (4), IMC 2012.
2. Revise detail 2/M300 to terminate the condensate at an approved location. Reference: Section 307.2.1, IMC 2012, as amended by the City of Tucson.
09/11/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Reqs Change Plan review has been completed and the following corrections are required. Please provide a written response to comments with plan re-submittal.

1) Clarify switching of fans in restrooms. Exhaust fans must be engaged whenever A/C system is running to eliminate the recirculation of air from the restrooms (reference IMC 403.2.1). This can be accomplished by swapping switch for a timer model that is set to be on whenever business is open, or you can interlock the exhaust fan with RTU 1.


If there are questions regarding this review contact:

LeeRay
520-837-4906
LeeRay.Hanly@tucsonaz.gov
09/11/2014 ROBERT SHERRY WATER REVIEW Completed
09/11/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET A000; MINIMUM PLUMBING FACILITIES: PER THE IBC TABLE 2902.1, THE REQUIREMENTS FOR WATER CLOSETS IS ONE/500 (MALE AND FEMALE), LAVATORIES ONE/750 (MALE AND FEMALE), AND DRINKING FOUNTAINS ONE/1000. REVISE THE COVER SHEET.
2. SHEET A001; DETAIL 6: DARKEN THE BRACING.
3. SHEET A001; DETAIL 6: REFERENCE IS MADE TO THE IBC SECTION 803.8 FOR INSULATION. REVISE THE REFERENCE TO THE 2012 IBC.
4. SHEET A002; DETAIL 3: IN ELEVATION C, ADD A VERTICAL GRAB BAR PER THE 2009 ICC/ANSI A117.1, FIGURE 604.5.1, AND YOUR DETAIL 4/A101.
5. SHEET A700: THE IBC SECTION 1607.14 REQUIRES INTERIOR WALL TO BE ABLE TO RESIST A MINIMUM HORIZONTAL LOAD OF 5 PSF. PROVIDE BRACING AT THE TOPS OF THOSE WALLS, INDICATING BRACING SIZE AND SPACING, AND THE CONNECTION OF THE BRACING TO THE TOP OF THE WALL AND TO THE STRUCTURE ABOVE.
6. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
09/11/2014 LOREN MAKUS ENGINEERING REVIEW Approved
09/11/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide automatic faucets for the lavatories, dispensing a maximum of 0.25 gallons per metering cycle. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson.
2. Provide tempered water for the lavatories and public hand-washing sinks in restrooms using approved devices conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2012.
09/11/2014 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/12/2014 MARTIN BROWN FIRE REVIEW Approved
09/23/2014 AROMERO4 WWM REVIEW Completed