Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL - BLDG/ZONING-WALKTHRU
Permit Number - T14CM05905
Review Name: RESIDENTIAL - BLDG/ZONING-WALKTHRU
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/09/2014 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 09/22/2014 | STEVE SHIELDS | ZONING | REVIEW | Denied | P&DS TRANSMITTAL FROM: Steve Shields, Lead Planner PROJECT: T14CM05905 422 N. Plumer Ave New SFR with detached carport TRANSMITTAL: September 22, 2014 COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1). This site is located in the R-1 zone (UDC 4.7.8). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9. The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure's wall facing each interior property line (Table 6.3-2.A). based on a wall height of 10'-8" the required perimeter yard setback from the proposed SFR to the north property line is 7'-2", proposed is 4'-6". Based on a wall height of 10'-5" the required perimeter yard setback from the proposed carport to the north property line is 6'-11", proposed is 4'-6". |
| 09/22/2014 | SSHIELD1 | NPPO | REVIEW | Passed | |
| 09/29/2014 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 09/29/2014 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Needs Review |