Permit Number: T14CM05899
Parcel: 11305058A

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T14CM05899
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/21/2014 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Reqs Change PLAN REVIEW COMMENTS
Date: 11-21-14
Activity: T14CM05899
Address: 1921 E. Greenlee
Applicant: Inai Maldonado

This letter reflects comments to be addressed. The purpose of this review is to verify compliance to the 2012 International Residential Code with local amendments. In order to facilitate a shorter back check time, we request that you please provide two complete sets of revised plans and calculations, along with a written response to each of the noted items indicating action taken. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

INCLUSIVE HOME DESIGN:
1. Provide a complete set of notes on the plan to meet the Inclusive Home Design Ordinance 10463.
2. Indicate the accessible route from the public way extending throughout the entire first floor (except for exempt areas as defined in section 1003.3), 1003.2. Vertical changes in floor elevation may not exceed ¼ inch (½ inch when beveled), 1003.4.

FLOOR PLAN:
3. Specify all door sizes.
4. Specify cement, fiber-cement, or glass-mat board backing in tub/shower enclosures, R307.2, R702.4.2.
5. Show the location of the attic access in a hallway or other readily accessible location with a minimum opening size 22"x30", R807.
6. Specify fireplace hearth size and materials, R1001 or R1004.

STRUCTURAL / FRAMING PLAN:
7. Provide wall bracing at dining room bay window that complies with R602.10.4.2.
8. Include a section detail for the ledger condition at exterior porches. Detail must include rafter connection to ledger and ledger connection to wall.

ELEVATIONS:
9. Provide an attic space ventilation calculation and note the size and location of all attic vents needed to comply, R806.2.
10. Show fireplace chimney on elevation drawings with a minimum 2' height above any roof point within 10' and not less than 3' above penetration, R1003.9.

PLUMBING PLAN:
11. Provide gray water segregation for at least one (1) bathing fixture or clothes washing machine Ordinance #10579/11089 revised July 9, 2013
12. Cleanouts are required at the kitchen sink area (State amendment) and upstream origination of drainage line, P3005.2.2.

MECHANICAL PLAN:
13. Provide manufacturer's cut sheet for package air conditioning unit listed for indoor installation.
14. Provide Manual J/S/D calculations for the forced air unit in accordance with M1401.3, M1601.1.
15. Specify the dryer vent size and location of termination, M1502.
16. Show exhaust fan capacity for kitchen hood, R303.3, M1507.

ELECTRICAL PLAN:
17. Kitchen small appliance receptacles shall not share lighting circuit, E3901.3.
18. Specify faceplate grounding per E4001.11.1.
19. Specify tamper resistant receptacles per E4002.14.
20. Indicate location of water heater disconnect switch, E4101.5.
21. Laundry room receptacles require at least one 20-amp circuit that shall serve no other outlets, E3703.3, 3901.8.
22. Show receptacle outlets at wall spaces 2' or more in the master bedroom so that no point along the wall (excluding door openings) is more than 6' from a receptacle outlet, E3901.2.
23. Dedicated bathroom circuit may not share closet lighting, E3703.4, E3901.6.
24. Provide carbon monoxide alarms per R315. Alarms must be installed in residences with attached garages and/or fuel-fired appliances when any work is performed that requires a permit.
25. Clarify exterior lighting reference in den.
26. GFCI protection required for all receptacles located in the garage, E3902.

OUTDOOR LIGHTING CODE
27. Provide cut sheets for all FCO fixtures showing the angle of cutoff, light emissions and fixture wattage. All other fixtures are assumed to be unshielded (non-FCO style) 104.2.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Clayton.Trevillyan@tucsonaz.gov
Residential Plan Review