Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T14CM05877
Parcel: 13423411B

Address:
135 S WILMOT RD

Review Status: Completed

Review Details: WALK THRU - COMM

Permit Number - T14CM05877
Review Name: WALK THRU - COMM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/19/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide copies of the NFRC certifications for the fenestration. [Third comment: Coordinate the fenestration U-values and SHGC numbers with the data from the window manufacturer.] [Second comment: If the NFRC certification numbers are not shown on the envelope compliance certificate, the default U-factor and SHGC values from Tables C303.1.3 (1) and C303.1.3 (2), IECC 2012 must be used to determine if the activity complies with the requirements of the IECC.] [Initial comment: Provide the NFRC certification number for the U-factor and the Solar Heat Gain Coefficient (SHGC) of the fenestration on COMcheck or use the appropriate default U-factor and SHGC values from Tables C303.1.3 (1) and C303.1.3 (2), IECC 2012. Coordinate the U-factor and the SHGC values shown on the COMcheck Envelope Compliance Certificate with the window descriptions shown on the drawings. Reference: Section C303.1.3, IEC 2012.]
02/19/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change The submitted calculations are based on Type L copper and Schedule 40 carbon steel piping, not PEX. The calculations are also too small to be read (Use 3/32" font). Third comment: Submitted calculations are not coordinated with this building.] [Second comment: Calculations not found in this submittal.] [Initial comment: Provide calculations showing how the PEX water supply tubing has been sized. Reference: Sections 604.1 and 604.3, IPC 201.]