Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T14CM05877
Parcel: 13423411B

Address:
135 S WILMOT RD

Review Status: Completed

Review Details: WALK THRU - COMM

Permit Number - T14CM05877
Review Name: WALK THRU - COMM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/04/2015 KEN VAN KARSEN ELECTRICAL-COMMERCIAL REVIEW Completed
02/04/2015 ROBERT SHERRY WATER REVIEW Completed
02/04/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. No site plan was included in this submittal. An approved development plan is not to be used for construction of on-site utilities (e.g. water service to the building, building sewer, site lighting, or electrical service to the building). [Initial comment: Provide a site utility drawing. Show the size and route of the building water supply along with the location and size of both the water meter and the reduced pressure principle backflow preventer assembly. Show the location of the proposed gravity grease interceptor, the size, route, and slope of the building sewer, the location of all cleanouts in the building sewer, and the location of the connection of the building sewer to the public sewer. Coordinate the location of the connections of the building drain and the gravity grease interceptor with the building sewer. Reference: Section 107.2.1, IBC 2012.]
2. Submitted calculations are not coordinated with this building. [Second comment: Calculations not found in this submittal.] [Initial comment: Provide calculations showing how the PEX water supply tubing has been sized. Reference: Sections 604.1 and 604.3, IPC 201.]
3. See Section 1003.3, IPC 2012, as amended by the City of Tucson for required calculations. [Second comment: Revise the gravity grease interceptor sizing calculations to include only those fixtures shown on the plans that will pass through the interceptor (e.g. no water closets, etc).] [Initial comment: Provide sizing calculations for the gravity grease interceptor. Reference: Section 1003.3, IPC 2012, as amended by the City of Tucson.]
02/04/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Coordinate the fenestration U-values and SHGC numbers with the data from the window manufacturer. [Second comment: If the NFRC certification numbers are not shown on the envelope compliance certificate, the default U-factor and SHGC values from Tables C303.1.3 (1) and C303.1.3 (2), IECC 2012 must be used to determine if the activity complies with the requirements of the IECC.] [Initial comment: Provide the NFRC certification number for the U-factor and the Solar Heat Gain Coefficient (SHGC) of the fenestration on COMcheck or use the appropriate default U-factor and SHGC values from Tables C303.1.3 (1) and C303.1.3 (2), IECC 2012. Coordinate the U-factor and the SHGC values shown on the COMcheck Envelope Compliance Certificate with the window descriptions shown on the drawings. Reference: Section C303.1.3, IEC 2012.]
02/04/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved