Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T14CM05666
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/29/2014 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
08/29/2014 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
08/29/2014 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Completed | |
08/29/2014 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
08/29/2014 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
09/02/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Clarify the stairwell through which the exhaust duct is being routed; is it a rated stairwell. |
09/02/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
09/02/2014 | ROBERT SHERRY | WATER | REVIEW | Completed | |
09/02/2014 | CARL SCHULTZ | FIRE | REVIEW | Denied | PLEASE PROVIDE FOR FOLLOWING INFOMATION: 1. OCC LOAD AND EXITING REQUIRMENTS 2. EM LIGHTING FOR THE FRONT PAINT ROOM IFC 1006.3 |
09/04/2014 | CPIERCE1 | WWM | REVIEW | Completed |