Permit Number: T14CM05612
Parcel: 113100080

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM05612
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/27/2014 MICHAEL ST. PAUL ZONING REVIEW Needs Review
08/27/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
08/27/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Completed
08/27/2014 ROBERT SHERRY WATER REVIEW Completed
08/27/2014 MARTIN BROWN FIRE REVIEW Approved
08/27/2014 LOREN MAKUS ENGINEERING REVIEW Approved
08/27/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
08/28/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Needs Review 1. SHEETS A1, A2, AND A3; KEY NOTES: IT APPEARS NOT ALL OF THE KEY NOTES LISTED ARE SHOWN ON THE PLANS, SECTIONS, AND DETAILS. VERIFY.
2. SHEETS S1.0, S1.1, S1.2, S1.3, AND S3.0: PROVIDE THE PROFESSIONAL SEAL ON THESE SHEETS.
3. SHEET S2.0; FOUNDATION PLAN: ENLARGE NOTE REFERENCES 1 AND 5 ON THE RIGHT SIDE PLAN.
4. SHEET S3.1: DARKEN THE EXISTING ELEMENTS.
5. SHEET S3.1; DETAIL 305: AT THE TOP OF THE NEW 2X6 STUD WALL, A REFERENCE IS MADE TO 2X12 BLOCKING. REVISE.
6. GENERAL: PROVIDE STRUCTURAL CALCULATIONS FOR THIS PROJECT.
7. GENERAL: PROVIDE RESPONSES TO THE COMMENTS.
08/28/2014 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/03/2014 SPOWELL1 WWM REVIEW Needs Review