Permit Number: T14CM05598
Parcel: 106042460

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T14CM05598
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/02/2015 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Reqs Change Date: 12-16-14
Activity: T14CM05598
Address: 211 E Navajo Rd #2 - 3rd review
Applicant: Robert Logan

FOUNDATION PLAN:
1. Previous comments have requested a floor or landing outside exterior doors (R311.3) and stair information based on the finished floor height above grade (R311.7.5). The proposed stairway does not include information regarding the maximum riser height or minimum tread depth and has been indicated to be located over the proposed landing. Specify the stair dimensions with the appropriate landing at the base of the stairway.

MECHANICAL PLAN:
2. Previous comments have requested Manual J/S calculations for the proper sizing of mechanical units (M1401.3, M1601). Information has been provided regarding the proposed mechanical units but the calculations as required by the International Energy Conservation Code have not been submitted.

OUTDOOR LIGHTING CODE
3. Previous comments have requested compliance with the City of Tucson's Outdoor Lighting Code. The calculation provide only includes three exterior lights, none of which are located on the proposed building. Include all exterior lighting on the property in the outdoor lighting calculation including the (4) lights proposed on the new buildings and any lighting located at exterior doors on the existing residence. Cut sheets must be provided for lighting fixtures in order to qualify as fully shielded. The one cut sheet provided does not qualify as a fully shielded fixture with a glass cover over the bulb.

Please contact us at your earliest convenience to arrange a meeting with the both the designer and property owner in order to resolve the remaining comments so that we may issue your permit.

Regards,

Clayton Trevillyan
520.837.4913
Clayton.Trevillyan@tucsonaz.gov
Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
01/12/2015 SHANAE POWELL OUT TO CUSTOMER Completed
01/12/2015 CPIERCE1 REJECT SHELF Completed