Permit Number: T14CM05598
Parcel: 106042460

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T14CM05598
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/24/2014 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Reqs Change PLAN REVIEW COMMENTS
Date: 10-24-14
Activity: T14CM05598
Address: 211 E Navajo Rd #2 - 2nd review
Applicant: Robert Logan

1. Provide consistent page sizes for the plan set, R106.1.1.

FOUNDATION PLAN:
1. Provide a floor or landing outside exterior doors, R311.3.
Note: The maximum allowable step height is 7.75 inches, R311.7.5. Having a landing 23 inches below the finished floor elevation would exceed this limit.

MECHANICAL PLAN:
2. Provide Manual J/S calculations for the forced air units in accordance with M1401.3, M1601.1.
Note: Having three mechanical systems per room would suggest that heating and cooling loads have not been considered for a complete system that meets the intent of the International Energy Conservation Code.

ELECTRICAL PLAN:
3. Specify faceplate grounding per E4001.11.1.
4. Specify tamper resistant receptacles per E4002.14.

OUTDOOR LIGHTING CODE
5. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 3.1.2. Include all exterior fixtures on the property in the calculations.
6. Provide cut sheets for all FCO fixtures showing the angle of cutoff, light emissions and fixture wattage. All other fixtures are assumed to be unshielded (non-FCO style) 104.2.
Note: Outdoor lighting must be justified. 'Jelly jar' lighting fixtures would be considered unshielded lighting and must conform to appropriate limits for the area.

INTERNATIONAL ENERGY CONSERVATION CODE:
7. Specify a "U" factor and solar heat gain coefficient of the windows and doors that meets or exceeds the requirements of N1102.1. The simplified prescribed energy value for climate zone 2B glazing is U=0.40 and skylights is U=0.65, the default SHGC is 0.25.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Clayton.Trevillyan@tucsonaz.gov
Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
10/27/2014 CPIERCE1 REJECT SHELF Completed