Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T14CM05574
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/10/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Revise the plumbing drawings to show the gas piping to the paint booth and to the paint prep and paint mixing room if required. |
| 10/10/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Revise the mechanical drawings to show the paint booth, paint mixing, and paint prep areas. Provide the balancing data for exhaust and makeup air flows for each area. |
| 10/14/2014 | MARTIN BROWN | FIRE | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/17/2014 | AROMERO4 | APPROVAL SHELF | Completed |
| 10/17/2014 | AROMERO4 | OUT TO CUSTOMER | Completed |
| 10/17/2014 | AROMERO4 | REJECT SHELF | Completed |