Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T14CM05518
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/25/2014 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 08/25/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Show the size, route, and termination of the condensate drains. |
| 08/25/2014 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Completed | |
| 08/25/2014 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 08/25/2014 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Reqs Change | Please provide structural calculations and details for the new roof top mounted HVAC units and the suspended fan coil units. END OF REVIEW |
| 08/25/2014 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 08/25/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Provide listing information from the manufacturer of the dishwasher stating that hot water is not required for proper operation. Reference: Section 303.2, IPC 2012. |
| 08/25/2014 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 08/25/2014 | RONALD BROWN | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 08/27/2014 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/27/2014 | AROMERO4 | APPROVAL SHELF | Completed |
| 08/27/2014 | AROMERO4 | OUT TO CUSTOMER | Completed |
| 08/27/2014 | AROMERO4 | REJECT SHELF | Completed |