Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - NEW
Permit Number - T14CM05499
Review Name: COMMERCIAL - NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/25/2014 | MARTIN BROWN | FIRE | REVIEW | Denied | Please indicate location of existing and/or proposed fire hydrants, with dimensions to property lines. Chapter 5 of the 2012 International Fire Code gives guidance as far as spacing requirements. Please indicate approximate location of underground fire sprinkler supply line and Fire Department Connection. Please indicate on plans that fire sprinkler installation AND fire underground suppl;y line installation are deferred submittals requiring separate permits. |
| 10/01/2014 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Reqs Change | GENERAL 1. The following sheets have lettering smaller than the City of Tucson standard of 3/32" actual for both upper and lower case: TS1, 1 of 4, SP1. Please revise all the sheets and resubmit. 2. Provide certification for special inspectors. SHEET TS1 3. Change the code reference 2012 NEC to 2011 NEC. 4. Change the occupancy load from 20 to 21. SHEET A1.0 5. Provide an accessible counter at the reception counter as required by the ICC A117.1, Section 404.3 for appropriate approach. SHEET SP2.1 6. The detail of the suspended water heater 5/P2.1 is not the same as the structural detail 28/S1.4. Please reconcile and resubmit. SHEET S1.4 7. At detail 23 call out the web stiffiners and their size. 8. At detail 28, reference detail 23 for the top portion of the platform connection to the structural members above. AT SHEETS A1.0 AND A3.0 9. Please provide a testing lab fire rating assembly number for the 2 hour rated wall assembly description 6B and the 2 hour wall section detail 7A3.0. a. Also please provide the wall section for the adjacent building and it's testing lab assembly number. b. As there is a property line running between the two buildings, each abutting exterior wall must have a two hour fire wall rating. c. Also please verify with Zoning what approvals and legal documents must be obtained if any enchroachments occurr. END OF REVIEW |
| 10/02/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Provide the elevation of the upstream cleanout and the elevation of the finished floor. If the finished floor elevation of the building is less than 12 inches above the elevation of the next upstream cleanout in the private sewer collection system, a backwater valve shall be installed in the building sewer. |
| 10/02/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide the NFRC fenestration product ratings on which the U-factors and SHGC values used on COMcheck have been based or use the appropriate default U-factors and SHGC values from Tables C303.1.3 (1) and C303.1.3 (2), IECC 2012. Show the required U-factors for the vertical glazing on the drawings. Reference: Section C303.1.3, IEC 2012. 2. Show how a continuous layer of insulation (R-4) is to be installed on the east and west exterior walls. Reference: Section 303.2, IECC 2012. 3. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012. |
| 10/02/2014 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 10/07/2014 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 10/08/2014 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Completed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/29/2014 | CPIERCE1 | REJECT SHELF | Completed |