Permit Number: T14CM05478
Parcel: 11005093F

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T14CM05478
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/12/2014 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Reqs Change PLAN REVIEW COMMENTS
Date: 9-15-14
Activity: T14CM05478
Address: 4640 E. San Francisco
Applicant: Stephen Curti

This letter reflects comments to be addressed. The purpose of this review is to verify compliance to the 2012 International Residential Code with local amendments. In order to facilitate a shorter back check time, we request that you please provide two complete sets of revised plans and calculations, along with a written response to each of the noted items indicating action taken. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

STRUCTURAL / FRAMING PLAN:
1. Provide braced wall panels and a continuous footing under exterior wall located along east side of addition, R403.1, R602.10.2.
2. Clarify the proposed roof covering material for the addition. Details 1 & 2 sheet A-2 are not consistent.

PLUMBING PLAN:
3. The IRC and UPC codes are not interchangeable. Revise references made to the UPC on sheet A-2.
4. Clarify the location of the 1" gas line specified on the Natural Gas Info table.
5. Indicate the location of the branch lines supplying the gas-fired range and furnace.

MECHANICAL PLAN:
6. Provide a mechanical equipment specification list, M1302.1.

ELECTRICAL PLAN:
7. Receptacles located outside the laundry area may not share the laundry circuit, E3703.3, 3901.8.

OUTDOOR LIGHTING CODE
8. Provide cut sheets for all FCO fixtures showing the angle of cutoff, light emissions and fixture wattage. Flood lighting is not considered fully shielded if the fixture is adjustable 104.2.

INTERNATIONAL ENERGY CONSERVATION CODE:
9. Specify the insulation material to be used that will provide R-38 in a 9.25" roof cavity.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Clayton.Trevillyan@tucsonaz.gov
Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
09/22/2014 CPIERCE1 OUT TO CUSTOMER Completed