Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T14CM05433
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/20/2014 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | PDSD TRANSMITTAL FROM: Steve Shields Lead Planner PROJECT: 1861 W Grant T14CM05433 Building Plan (1st Review) TRANSMITTAL DATE: August 20, 2014 1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 2. Provide a copy of the last approved site plan with an updated vehicle parking calculation that demonstrates that the required number of vehicle parking spaces are provided. Or provide the required documents per UDC Section 3.3.3.H. 3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved development package. Additional comments may be forthcoming. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 |
08/20/2014 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
08/20/2014 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
08/21/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012. |
08/21/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. The International Plumbing Code, 2012, is the controlling code for this activity, not the 2009 International Plumbing Code (Remove references to out-of-date codes from the plumbing general notes.). Reference: Section 101, IBC 2012. 2. Provide sufficient information to show that the installation of the new plumbing fixtures will not cause the existing water supply and sanitary waste systems to become overloaded (i.e. show the existing waste piping). Reference: Section 107.2.1, IBC 2012. 3. Provide a detail of the water heater installation, including the excess pressure relief, expansion tank, vacuum relief, safety pan, and valves. Reference: Sections 503, 504, 606.1, and 607.3, IPC 2012. 4. The minimum drain pipe size for a water closet is 3". |
08/21/2014 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Reduced pressure backflow prevention assemblies are required at the water meter for multi-use commercial buildings, not double check valves. Verify that there is an existing reduced pressure backflow prevention assembly serving this building. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://cms3.tucsonaz.gov/sites/default/files/water/docs/backflow-ordinance.pdf |
08/21/2014 | CARL SCHULTZ | FIRE | REVIEW | Approved | |
08/21/2014 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET CS; EGRESS PLAN: IN THE MERCANTILE SHOWROOM, THE OCCUPANT LOAD IS DETERMINED USING AN ALLOWABLE 200 SF/PERSON. TABLE 1004.1.2 INDICATES AN ALLOWABLE 30 SF/PERSON FOR A MERCANTILE GRADE FLOOR AREA. CLARIFY AND REVISE THE OCCUPANT LOAD AS REQUIRED. 2. SHEET CS; EGRESS PLAN: IN THE STORAGE WAREHOUSE, THE OCCUPANT LOAD IS DETERMINED USING AN ALLOWABLE 500 SF/PERSON. TABLE 1004.1.2 INDICATES AN ALLOWABLE 300 SF/PERSON FOR MERCANTILE STORAGE AREAS. CLARIFY AND REVISE THE OCCUPANT LOAD AS REQUIRED. 3. SHEET CS; BUILDING CODE REQUIREMENTS: ADD THE 2009 ICC/ANSI A117.1 ACCESSIBILITY CODE TO THIS LIST. 4. SHEET CS; SITE DATA SUMMARY TABLE; OCCUPANT LOAD CALCULATIONS: THE SITE DATA TABLE INDICATES 10,347 SF FOR THE BUILDING, WHILE THE OCCUPANT LOAD CALCULATIONS INDICATE 10,215 SF. CLARIFY. 5. SHEET A1.0 (FLOOR PLAN); WALL LEGEND: WALL TYPE 4 WAS NOT LOCATED ON THE PLAN. VERIFY. 6. SHEET A1.0 (FLOOR PLAN); KEYED NOTES: IN ROOM 104, NOTE 1 IS INDICATED BY THE WINDOW. IS THIS LOCATION CORRECT? 7. SHEET A1.0 (FLOOR PLAN); KEYED NOTES: NOTE 12 WAS NOT LOCATED ON THE PLAN. VERIFY. 8. SHEET A1.0; FLOOR PLAN: THE IBC TABLE 2902.1 INDICATES A HIGH/LOW DRINKING FOUNTAIN IS REQUIRED. NO DRINKING FOUNTAINS WERE LOCATED ON THE PLAN OR ON THE PLUMBING SHEETS. VERIFY. 9. SHEET A4.1; KEYED NOTES: NOTES 5 AND 6 REFERENCE 3/A4.1 FOR A FLUE SPACE. NOTE 6 IS INDICATED ON 2/A4.1, AND NOTE 5 IS NOT SHOWN. CLARIFY. 10. SHEET A5.0; SECTION 2: DARKEN THE DIMENSIONS. 11. SHEET A6.0; KEYED NOTES: NOTE 11 INDICATES A GRANITE COUNTER TOP. CLARIFY. 12. SHEET A6.0; KEYED NOTES: NOTE 12 IS NOT INDICATED ON THE ELEVATIONS. VERIFY. 13. SHEET A6.0; KEYED NOTES: NOTE 14 INDICATES AN ACCESSIBLE URINAL. CLARIFY. 14. SHEET A8.0: THE IBC SECTION 1607.14 REQUIRES INTERIOR PARTITIONS TO WITHSTAND A 5 PSF HORIZONTAL LOAD. INDICATE, ON THE DRAWINGS, BRACING AT THE TOP OF THE WALLS THAT WILL PROVIDE THAT CAPABILITY. INCLUDE BRACING SIZE, SPACING, AND CONNECTIONS TO THE TOP OF THE WALL AND TO THE STRUCTURE ABOVE. INCLUDE SUPPLEMENTAL BRACING SUPPORTS AT THE EXISTING STRUCTURE ABOVE AS REQUIRED. 15. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
08/22/2014 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Restroom exhaust fans are shown switched with lights. Provide interlocks with the associated RTU's or provide programmable time switches so that EF's are on during all business hours. Ref IMC 403.2.1 (cannot recirculate air from restrooms) |
09/15/2014 | SPOWELL1 | WWM | REVIEW | Needs Review |