Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T14CM05375
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/16/2014 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Plan review has been completed and the following corrections are required. Please provide a written response to comments with plan re-submittal. 1) Provide 2012 City of Tucson Outdoor Lighting Code compliance information. Fixtures noted are not full cut-off under the canopy therefore a complete site lighting inventory may be necessary. If there are questions regarding this review contact: LeeRay 520-837-4906 LeeRay.Hanly@tucsonaz.gov |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
09/17/2014 | SHANAE POWELL | APPROVAL SHELF | Completed |
09/17/2014 | SHANAE POWELL | OUT TO CUSTOMER | Completed |