Permit Number: T14CM05356
Parcel: 137055310

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM05356
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/11/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Coordinate the components shown on the Mechanical Compliance Certificate with the design shown on the plans. The plans show a 5-ton RTU and a 7.5-ton RTU but the Mechanical Compliance Certificate shows only one 12-ton RTU. [Second comment: The Mechanical Compliance Certificate was not included in this submittal.] [Initial comment: Provide the Mechanical Compliance Certificate to demonstrate that the new HVAC equipment complies with the 2012 International Energy Code.]